The Micro+Plus Bio-Tech module is a permanent hood with a replaceable gel seal HEPA or ULPA filter. The gel seal filter can be installed, replaced and tested from inside the room without removing or disturbing the permanent hood. The low profile design is only 9" high (excluding collar).

Applications
These unit are designed for cleanrooms requiring ultra clean air from ISA Class 1 to Class 6. They are ideally suited for installations that are certified frequently and where minimizing downtime is critical. Pharmaceutical and bio-tech industries are representative of these critical applications.

Operation
The modules are designed for lay in installation in standard 1-1/2" or 2" T-Bar ceiling grids or hard ceilings. Incoming air is supplied to the units through a flexible duct connected to the inlet collar. Air flow is distributed evenly over the face of the filter by an air distribution plate mounted inside the housing below the inlet collar. A butterfly damper in the collar allows adjustment of air flow through the unit to facilitate balancing the room. A removable stainless steel grille mounted on the downstream side of the housing protects the filter and helps create uniform air flow into the clean space.

Construction Features

Housing- Constructed of .063 aluminum or 304 stainless steel with a 10" or 12" inlet collar.

Welded Seams- All straight seams are continuously welded to assure leak free construction. All other joints are intermittently welded and sealed with RTV sealant.

Butterfly Damper- Air flow balancing is controlled by a butterfly damper adjustable from inside the room.

Stainless Steel Grille- A stainless steel grille fits flush with the housing and is easily removable from inside the room without disturbing the filter. The grille is a perforated plate, 40% open.

Reverse Gel Seal HEPA Filter- The reverse gel seal cell side design allows the filter to be inserted up into the housing minimizing overall height of the unit and maintaining a flush fit in the ceiling grid. The standard unit is 99.99% efficient of 0.3 micron particles.

Static Pressure/Sampling Port- A port is accessible from inside the room to measure static pressure or sample the upstream aerosol concentration during ton site certification testing.

Options
ULPA filters (99.9995% on .12 microns)
Extended stainless steel grille
Undersized unit for 2" T-Bar ceiling grid
Hanging tabs
Aerosol dispersion nozzle
Aerosol dispersion quick disconnect
Foil insulation
stainless steel trim for installing sheet rock or plaster ceiling. (5/8" or 1-1/2" wide)

 

Micro+Plus Dimensions

Call Toll Free 1-800-334-9142